What PUE does Malaysia require for data centres?

MITI’s PUE figures are design targets, not operating limits. For data centres applying for the DESAC incentive, MITI’s guideline proposes a design PUE of 1.4 for hyperscale (132 kV and above, over 21.25 MW), 1.6 for purpose-built colocation built after 2020 in that band, and 1.7 for others (0.85 to under 21.25 MW). It also recommends a design WUE of 2.2 m³ per MWh of IT energy or lower.

MITI efficiency targets
RuleWhat it saysApplies to
PUE (MITI guideline)Proposed design PUE: 1.4 for hyperscale (132 kV and above, over 21.25 MW); 1.6 for purpose-built colocation built after 2020 in that band; 1.7 for others (0.85 to under 21.25 MW)Applicants for the DESAC incentive; not an operating limit
WUE (MITI guideline)Recommended design WUE of 2.2 m³ per MWh of IT energy or lowerSame
CUE (MITI guideline)Grid factor × PUE. The guideline uses 0.758 (2021); the current Peninsular factor is 0.740 (2024, provisional)Same

Johor separately sets an allowable WUE of 1.8, unit not published. Read as litres per kWh, it is stricter than MITI’s 2.2.